Security Ranger III Guia do Utilizador Página 49

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 48
Performing an IR Quick Read
1. Connect the IR cable to the nine-pin serial port on
the bottom of the handheld.
2. Align the optical read head of the IR cable with the
endpoint IR port.
3. Tap Read.
Result: The screen lls with endpoint information and
the buttons become active.
Start, Pause, Stop – Radio Modes
Figure 82: ORION ME IR Programming screen
ORION endpoints are programmed at the factory to begin sending meter readings when the register senses flow through
the meter. As a result, ORION ME and SE endpoints can be installed on meters without having to manually start the endpoint.
When water usage has been registered on the meter, the endpoint sends a signal every five to six seconds.
The following statuses may display in the Radio field on the ORION ME IR screen.
Stopped Stops the endpoint from transmitting. A stopped endpoint must be reprogrammed to begin
transmitting again. Any stored historical endpoint interval data (profile data) will be cleared when the
endpoint is restarted.
Paused Pauses the endpoint transmission temporarily until a unit of water or gas is registered. Commonly
used for seasonal customer accounts.
On-Mobile Mode An ORION ME or SE endpoint begins in mobile mode and continues to transmit in mobile mode until
and unless communication is established with an ORION SE network gateway transceiver. An endpoint
in mobile mode sends a message requesting gateway assignment once every 12 hours. If a gateway
responds with an assignment using two-way communication, the endpoint automatically switches to
On-Fixed Mode. Fixed mode transmissions cannot be received by the handheld transceiver.
Discovery Mode For troubleshooting only. To be used under the direction of Badger Meter Technical Support.
On-Fixed Mode An endpoint in On-Fixed Mode is assigned to an ORION SE network gateway transceiver for xed
network data collection. An endpoint in On-Fixed Mode will not transmit mobile messages. It reverts
to On-Mobile Mode if the endpoint fails to receive a response from a gateway for four consecutive
days. Once communication has been re-established with the gateway, the endpoint automatically
transitions to On-Fixed Mode.
The Start button is used to start an endpoint before usage is registered. Align
the optical head on the IR cable with the endpoint IR port and tap Start.
The Pause button is used to pause the radio signal temporarily. Align the optical
head on the IR cable with the endpoint IR port and tap Pause. The endpoint
begins transmitting again when a unit of water is registered from the meter.
The Stop button is used to stop an endpoint from sending a signal, regardless of
the usage registered from the meter. Align the optical head on the IR cable with
Figure 83: Radio modes
the endpoint IR port and tap Stop. The Start button must be used to turn the endpoint on again. The endpoint history
(profile data) is cleared when the endpoint is restarted.
NOT: N Stopped radios must be restarted using the Start function and will not automatically restart when usage is registered
from the meter. When used with an RTR, the odometer value must also be programmed to reflect the current
registration reading. When used with an ADE, the odometer value is automatically updated within the hour.
Installation & Operation Manual